Vista de pagina 90
IB-23C650
SETUP
Table 7. Auto/Manual Ratio Bias Setup Menu
Middle
Display
Bottom
Display
Entry Description
SOURCE LOCAL
REMOTE
Initial value can be set in "TUNE MENU",
Table 12, and Ratio can be changed in
operator's display.
Initial value can be viewed in "TUNE MENU",
Table 12, and Ratio can be viewed in
operator's display.
Note: Only one remote source is allowed. If
ratio is REMOTE, bias must be LOCAL.
SOURCE LOCAL
REMOTE
Same as Step 7.
Same as Step 7.
Note: Only one remote source is allowed. If
ratio is REMOTE, bias must be LOCAL.
BALANCE STANDARD
AUTO
= Outputs may bump when switching from
manual to auto
= Bumpless transfer when switching from
manual to auto. Not valid if source is
remote. Calculated value of ratio can exceed
30000 during normal operation.
See Step 5 for explanation of calculation.
BALANCE STANDARD
AUTO
= Outputs may bump when switching from
manual to auto
= Bumpless transfer when switching from
manual to auto. Not valid if source is
remote. Calculated value of ratio can exceed
30000 during normal operation.
See Step 5 for explanation of calculation.