IB-23C650
CALIBRATION DATA
Table 15. Main/Option Board Calibration (Base Configuration Menu)
Step Step Description
Top
Display
16
Main Board Calibration.
UP
begins calibration at Step 16.1 (Factory
ONLY).
SCRL
advances to Step 17 (Option Board
Calibration).
MAIN BRD
16.1
Process Input Voltage Ref. High
UP
begins entry at most significant digit. Use
UP
or
DN
to set the digit, then
SCRL
to scroll to the
next digit. Repeat for all digits.
SCRL
advances to:
Step 16.1.1 if value was changed.
Step 16.2 otherwise.
PROC INP
16.1.1
Are You Sure You Want to Change Process
Vref Hi?
UP
selects YES or
DN
selects NO.
SCRL
advances to:
Step 16.1 on NO.
Step 16.2 on YES.
ARE YOU
16.2
Process Input Voltage Ref. Low
UP
begins entry at most significant digit. Use
UP
or
DN
to set the digit, then
SCRL
to scroll to the
next digit. Repeat for all digits.
SCRL
advances to:
Step 16.2.1 if value was changed.
Step 16.3. otherwise.
PROC INP
16.2.1
Are You Sure You Want to Change Process
Vref Lo?
UP
selects YES or
DN
selects NO.
SCRL
advances to:
Step 16.2 on NO.
Step 16.3 on YES.
ARE YOU
206