IB-23C650
CALIBRATION DATA
Table 15. Main/Option Board Calibration (Base Configuration Menu)
Middle
Display
Bottom
Display
Entry Description
MR RATIO xxxxxxxx
= Any hexadecimal digit.
See note on Step 17.
SURE? YES
NO
This step is present only to guard against
accidentally changing this critical calibration
value.
CKT COMP xxxxxxxx = Any hexadecimal digit.
See note on Step 17.
SURE? YES
NO
This step is present only to guard against
accidentally changing this critical calibration
value.
MA RATIO xxxxxxxx = Any hexadecimal digit.
See note on Step 17.
SURE? YES
NO
This step is present only to guard against
accidentally changing this critical calibration
value.
213