IB-23C650
SETUP
Table 5. Output Relays Setup Menu
Middle
Display
Bottom
Display
Entry Description
**MENU**
None.
SETUP None.
FUNCTION NONE
ALARMS
TOTALIZE
RAMPSOAK
REM/LOC
AUTO/MAN
MANUAL
CMP ONLY
Note: If relay is used for control (per output
type in BASE CGF), ‘CONTROL’ will appear for
one second and displays will advance to Relay
B Setup.
= Relay action controlled from front panel
= Relay action controlled by computer
TRIP ACT 1
2
3
4
1234
15 possible combinations of the four display
alarms. Any of the alarms in the chosen set
will cause the relay to trip (de-energize). (See
Alarm Section.) All must be off to release
(energize) it.
Valid combinations are: 1, 2, 3, 4, 12, 13, 14,
23, 24, 34, 123, 124, 134, 234, and 1234.
SETUP None.
FUNCTION NONE
ALARMS
TOTALIZE
RAMPSOAK
REM/LOC
AUTO/MAN
MANUAL
CMP ONLY
Note: If relay is used for control (per output
type in BASE CGF), ‘CONTROL’ will appear for
one second and displays will advance to Relay
C Setup.
= Relay action controlled from front panel
= Relay action controlled by computer
77