Micromod MOD: Modcell 2050R Users Guide Manual de usuario Pagina 85

  • Descarga
  • Añadir a mis manuales
  • Imprimir
  • Pagina
    / 228
  • Tabla de contenidos
  • SOLUCIÓN DE PROBLEMAS
  • MARCADORES
  • Valorado. / 5. Basado en revisión del cliente
Vista de pagina 84
IB-23C650
SETUP
Table 5. Output Relays Setup Menu
Middle
Display
Bottom
Display
Entry Description
TRIP ACT 1
2
3
4
1234
15 possible combinations of the four display
alarms. Any of the alarms in the chosen set
will cause the relay to trip.
Valid combinations are: 1, 2, 3, 4, 12, 13, 14,
23, 24, 34, 123, 124, 134, 234, and 1234.
SETUP None.
FUNCTION NONE
ALARMS
TOTALIZE
RAMPSOAK
REM/LOC
AUTO/MAN
MANUAL
CMP ONLY
= Relay action controlled from front panel
= Relay action controlled by computer
TRIP ACT 1
2
3
4
1234
15 possible combinations of the four display
alarms. Any of the alarms in the chosen set
will cause the relay to trip.
Valid combinations are: 1, 2, 3, 4, 12, 13, 14,
23, 24, 34, 123, 124, 134, 234, and 1234.
79
Vista de pagina 84
1 2 ... 80 81 82 83 84 85 86 87 88 89 90 ... 227 228

Comentarios a estos manuales

Sin comentarios