IB-23C650
SETUP
Table 9. Ramp/Soak Profile Setup Menu
Middle
Display
Bottom
Display
Entry Description
START SP xxxx
Between ‘Local Set-point Low Limit’ and ‘Local
Set-point High Limit’
Note: If a decimal point change is made in the
INPUTS **MENU** after configuring the ramp /
soak profile, the profile will require
reconfiguration.
END SP xxxx Between ‘Local Set-point Low Limit’ and ‘Local
Set-point High Limit’
SOAK TIM xxx.x 0 to 3000.0 (hours or minutes, per Time Units,
Step 6)
RMP RATE xxx.x Change per unit time (hours or minutes) in
engineering units
Example: a ramp of 10 degrees at 2
degrees every minute, and time unit =
minutes, then the value = 2.0. The
Displays ramp/soak status display
indicates minutes remaining and counts
down from 5 minutes.
Note: Ramp rates excessively high could cause
the ending set-point to be exceeded. Will be
corrected when next segment starts. Ramp
rates excessively low over a wide range cannot
be displayed properly in the time remaining
display in Displays. Maximum time shown is
3200 units of time; display will decrement when
time remaining is less than 3200.
97