Micromod MOD: Modcell 2050R Users Guide Manual de usuario Pagina 123

  • Descarga
  • Añadir a mis manuales
  • Imprimir
  • Pagina
    / 228
  • Tabla de contenidos
  • SOLUCIÓN DE PROBLEMAS
  • MARCADORES
  • Valorado. / 5. Basado en revisión del cliente
Vista de pagina 122
IB-23C650
SETUP
Table 12. Tune Menu
Middle
Display
Bottom
Display
Entry Description
ENABLE YES
NO
= Enable integral response
= Don’t enable integral response
HEAT xxx.xx 0.01 to 120.00 repeats/minute
COOL xxx.xx 0.01 to 120.00 repeats/minute
RESET xxx.xx 0.01 to 120.00 repeats/minute
MAN RSET NO
YES
= Must calculate manual reset value when
switching from manual to auto:
MR = Output – (Gain x Error)
= Fixes manual reset at value in Step 7.4.1
RESET xxx.x 0.0 to 100.0%
Note: Manual reset can be turned off by setting
this value to 0.
PREACT 0.0 to 3000.0 seconds
Derivative response