Micromod MOD: Modcell 2050R Users Guide Manual de usuario Pagina 161

  • Descarga
  • Añadir a mis manuales
  • Imprimir
  • Pagina
    / 228
  • Tabla de contenidos
  • SOLUCIÓN DE PROBLEMAS
  • MARCADORES
  • Valorado. / 5. Basado en revisión del cliente
Vista de pagina 160
IB-23C650
TUNING
Figure 17. Process Recovery Cycle with Optimum
Response Settings
Increasing the gain setting increases cycle B relative to cycle A. If the
controller has gain response only, no further adjustment is required. If the
controller has two or three responses, proceed to Step 7.
7. Measure the period (P) of oscillation in minutes. The period is the time
required for one complete cycle.
8. Calculate I (integral) and D (derivative) values as follows:
a. Controller with P and I responses:
I = P (Minutes)
155
Vista de pagina 160
1 2 ... 156 157 158 159 160 161 162 163 164 165 166 ... 227 228

Comentarios a estos manuales

Sin comentarios