IB-23C650
INSTALLATION
Figure 8. Millivolt Input Connections
Shield to be left uncon-
nected at this end.
Note: Terminals 12 & 13
must be wired
together for MV input.
MILLIVOLT INPUT
GROUNDED
mV
Source
– + G
UNGROUNDED
mV
Source
– + G
Shield to be left uncon-
nected at this end.
See Note
See Note
Millivolt input specifications are:
Input Range: –10 to 120 mV dc
Input Impedance: 10M ohms minimum
Resolution: 3 microvolts maximum, 0.003% of a typical 100 mV span
Accuracy: 0.08% of input or 20 microvolts, whichever is greater
Temperature Effect: 0.01% per degree C
Linearizations: Square law
Sample Time: 0.25 seconds
19