Command Series Migration to MOD 30ML
Pre-configured Single Loop PID Control
To change the display tag name for the PID:
Open the display block PID Display inside the compound FC156 PID (PV / LOCAL SP)
and change the Display Tag under the Display tab. See figure below:
Figure P1.4.
PID with Local SP
Display Block
The display tag name also needs to be entered into the DIF (Display Interface Block) at
the top level of the database. See the section: Procedure for adding the Display Tag to
the Display Interface Block in the chapter Introduction for more information.
P1- 7