Command Series Migration to MOD 30ML
Function Code 156 – PID with Local SP
S23 N/A N/A N/A
SPTI PID Input – Floating
Point
Setpoint track input. Connect to the
PID.SPTI signal of the compound.
To change the display tag name for the PID:
Open the display block PID Display and change the Display Tag under the Display tab.
See figure below:
Figure 156 .2.
Function Code
156
PID with Local SP
Display Block
The display tag name also needs to be entered into the DIF (Display Interface Block) at
the top level of the database. See the section: Procedure for adding the Display Tag to
the Display Interface Block in the chapter Introduction for more information.
156 - 4