Micromod RetroPAK: SLC Configuration Manual Manual de usuario Pagina 112

  • Descarga
  • Añadir a mis manuales
  • Imprimir
  • Pagina
    / 394
  • Tabla de contenidos
  • MARCADORES
  • Valorado. / 5. Basado en revisión del cliente
Vista de pagina 111
Command Series Migration to MOD 30ML
Pre-configured Dual Loop PID Control
Figure P2.3.
Dual loop
PID with Local SP
You will need to use a different input function block if the input selected in the AIN block
is other than voltage / current. Use the following rule:
Input Type Input Function block Type
Current, Voltage, Milli voltage VCI (voltage or current input)
TTI (thermocouple transmitter input)
RTTI (RTD transmitter input)
Thermocouple TI (thermocouple input)
RTD RTI (RTD Input)
Resistance RI (resistance Input)
Configuration of Input 2 is similar to this. The function blocks for input2 are AIN2 and
ENG UNITS 2.
P2- 6
Vista de pagina 111
1 2 ... 107 108 109 110 111 112 113 114 115 116 117 ... 393 394

Comentarios a estos manuales

Sin comentarios