
Command Series Migration to MOD 30ML
Pre-configured Dual Loop PID Control
Figure P2.3.
Dual loop
PID with Local SP
You will need to use a different input function block if the input selected in the AIN block
is other than voltage / current. Use the following rule:
Input Type Input Function block Type
Current, Voltage, Milli voltage VCI (voltage or current input)
TTI (thermocouple transmitter input)
RTTI (RTD transmitter input)
Thermocouple TI (thermocouple input)
RTD RTI (RTD Input)
Resistance RI (resistance Input)
Configuration of Input 2 is similar to this. The function blocks for input2 are AIN2 and
ENG UNITS 2.
P2- 6
Comentarios a estos manuales