Command Series Migration to MOD 30ML
Function Code 8 – Rate Limiter
To change the Increase Rate Limit S3:
Open the EX block INCLIM. Select the Inputs tab. Select the input S3 by double-
clicking on the number. The Specify Input Value dialog will be displayed as shown I the
next figure. Type the desired value in the Internal Data field.
Figure 8 .4.
Blocks Execution
Order after
rearranging
To change the Decrease Rate Limit S4:
Open the EX block DECLIM. Select the Inputs tab. Select the input S4 by double-
clicking on the number. The Specify Input Value dialog will be displayed as shown I the
next figure. Type the desired value in the Internal Data field.
8 - 4