Command Series Migration to MOD 30ML
Function Codes – Introduction
block or it can be an internal value in the PID block that can be manually changed by the
user from the faceplate.
This is in contrast to the SCL/CLC PID where the Track (S3 – Track Reference Signal) of
the PID block is enabled with the help of TS (S4 – track switch signal) for anti reset
windup during a Manual to Auto transfer. In the case of MOD 30ML/Modcell PID, this is
taken care automatically during the Manual/Auto transfer since the MOD 30ML/Modcell
PID block has the PID and M/A in one.
See the following figure where the Options tab of the PID block is shown:
Figure 1 .23.
PID Options Tab
We have made some changes to the default configuration of the PID block. Click on OK
to accept the changes and close the PID block.
1 - 28