Command Series Migration to MOD 30ML
Function Code 156 – PID Ratio with Remote SP
To enable feedforward control and change the feedforward type (S6):
Open the PID block and select the Options tab. See figure below:
Figure 156rr .3.
Function Code
156
PID Ratio with
Remote SP
Connect the desired signal to the feedforward input (PID.S6) of the compound.
156rr - 5