Command Series Migration to MOD 30ML
Pre-configured Single Loop PID with Remote SP
Figure P3 .3.
PID with Remote
SP
You will need to use a different input function block if the input selected in the AIN block
is other than voltage / current. Use the following rule:
Input Type Input Function block Type
Current, Voltage, Milli voltage VCI (voltage or current input)
TTI (thermocouple transmitter input)
RTTI (RTD transmitter input)
Thermocouple TI (thermocouple input)
RTD RTI (RTD Input)
Resistance RI (resistance Input)
Repeat this procedure to configure the input (AIN1) and signal conditioning block (VCI2)
for the remote setpoint input.
P3 - 6