Micromod RetroPAK: SLC Configuration Manual Manual de usuario Pagina 192

  • Descarga
  • Añadir a mis manuales
  • Imprimir
  • Pagina
    / 394
  • Tabla de contenidos
  • MARCADORES
  • Valorado. / 5. Basado en revisión del cliente
Vista de pagina 191
Command Series Migration to MOD 30ML
Pre-configured PID Ratio with Remote SP
Figure P6.3.
PID Ratio with
Remote SP
You will need to use a different input function block if the input selected in the AIN block
is other than voltage / current. Use the following rule:
Input Type Input Function block Type
Current, Voltage, Milli voltage VCI (voltage or current input)
TTI (thermocouple transmitter input)
RTTI (RTD transmitter input)
Thermocouple TI (thermocouple input)
RTD RTI (RTD Input)
Resistance RI (resistance Input)
Configuration of Input 2 (for the Remote setpoint PID.S2) is similar to this. The function
blocks for input2 are AIN2 and ENG UNITS 2.
P6- 6
Vista de pagina 191
1 2 ... 187 188 189 190 191 192 193 194 195 196 197 ... 393 394

Comentarios a estos manuales

Sin comentarios