Command Series Migration to MOD 30ML
Pre-configured Dual Loop PID with Remote SP
To change the value of the Output Limits (S16, S17):
Open the PID block and open the Output tab. Change the values for the Output Limits
Low and High and Output rangeLow and High.
See figure below:
Figure P4.11.
Dual PID with
Remote SP
P4- 14