Command Series Migration to MOD 30ML
Pre-Configured – Cascade Control
To configure the inputs:
Open the AIN block AIN1 for input 1. See figure below:
Figure P5.2.
Cascade PID
You can change the Input Type and Linearization Type for the built-in input 1 here.
Specify the Input Signal Range also.
The VCI block ENG UNITS 1 in the loop compound is used for converting the voltage,
millivolts or current input signal to engineering units. See figure below:
Change the Linearization type (Linear, Square, Square root, Modified Square, Modifed
Square root) as required for the input signal and specify the Engineering Range and
Quality Limits.
P5- 5