MOD 30ML Multiloop Controller
OPERATION
3-28
5. Tune the configured control parameters using the front panel keys as shown in the
illustration. The parameters available for tuning are as follows:
Parameters which are always available:
Action [ACTION], Gain [GAIN], Reset [RESET], Preact [PREACT], Set-Point Low
Limit [SP LOLIM], set-point high limit [SP HILIM], output low limit [OP LOLIM],
output high limit [OP HILIM].
Parameters which are available only when configured:
Filter type [FIL TYP], Filter Time [FIL TIME], Feed Forward Gain [FF GAIN], Feed
Forward Bias [FF BIAS], and Manual Reset [MAN RSET]. Prior to the
appearance of the feed forward gain and bias parameters, the Feed Forward
Type [FF TYPE] is identified on Line 6 as [MULT] or [ADD] for information only; it
is not tunable.
6. When the [EXIT] [TUNING] prompt appears after the last tuning display, proceed as
follows:
Press the R/L[PRV] key to return to the previous display.
Press the Scroll[NXT] key to return to the start of the tuning sequence.
Press the Up [] key to return to the runtime displays.