MOD 30ML Operation
SETUP
2-14
Table 8. User Compound Template Configuration (Cont’d)
Step Step Description Line 1 Line 2 Line 6 Entry Description
Volt, Milliamp and Millivolt Inputs Only:
8D4
(V, mA)
Process Input Low Signal
change value, ENT enters
NXT, PRV change step
PROC INP LO SIGNL
1.00
4.00
0.00
0% value in input units.
Volts
milliamps
millivolts
8D5
(V, mA)
Process Input High Signal
change value, ENT enters
NXT, PRV change step
PROC INP HI SIGNL
5.00
20.00
100.00
100% value in input units.
Volts
milliamps
millivolts
8D6
(V, mA)
Process Input Linearization
change value, ENT enters
NXT, PRV change step
PROC INP LINEARZT LINEAR
LINEAR,
MOD SQRT modified square root,
MOD SQR modified square,
SQ ROOT square root, or
SQUARE
Resistance Inputs Only:
8D4
(Res.)
Process Input Resistance Range
change value, ENT enters
NXT, PRV change step
PROC INP RES RNGE LOW
LOW (built-in = 0 to 55 ohms)
NORMAL (built-in = 0 to 430 ohms)
8D5
(Res.)
Process Input Low Signal
change value, ENT enters
NXT, PRV change step
PROC INP LO SIGNL 0.00
0% value in ohms.
8D6
(Res.)
Process Input High Signal
change value, ENT enters
NXT, PRV change step
PROC INP HI SIGNL 4000.00
100% value in ohms.
8D7
(Res)
Process Input Nominal Resistance
change value, ENT enters
NXT, PRV change step
PROC INP NOM RES 0.00
Resistance produced by RTD in
ohms at zero degrees Celsius.
Ranges are: 2-Wire module (0 to
4000), 3-Wire module (0 to 400),
BI AIN (0 to 430).
8D8
(Res.)
Process Input Leadwire Resistance
change value, ENT enters
NXT, PRV change step
PROC INP LW RES 0.00
Leadwire resistance in ohms.
Values that cause the sum of the
leadwire resistance and the input to
exceed maximum resistance will
cause an overrange error.
Thermocouple Inputs Only:
8D4
(TC)
Process Input Thermocouple Type
change value, ENT enters
NXT, PRV change step
PROC INP TC TYPE TC TYPEK
Types are: B, E, J, K, N, R, S, T.
8D5
(TC)
Process Input Temperature Scale
change value, ENT enters
NXT, PRV change step
PROC INP TEMPSCAL CELSIUS
Celsius
Kelvin
Rankine
Farenheit
8D6
(TC)
Process Input Zero
change value, ENT enters
NXT, PRV change step
PROC INP ZERO 0.00
Specify zero calibration value in
result units.
8D7
(TC)
Process Input Span
change value, ENT enters
NXT, PRV change step
PROC INP SPAN 1.00
One is nominal. Specify span
calibration value in result units.