MOD 30ML Multiloop Controller
OPERATION
3-10
3.9.1 Single Loop Automatic Operation with Local Set-Point
When a control loop is configured for single loop operation with local set-point, the front panel
displays and control key operations resemble the examples below.
[AUT] indicates that the controller is in automatic
mode.
[LOC] indicates local set-point. R/L key is disabled.
[SP] indicates that the current set-point value is
displayed on Line 6 (bottom line). An engineering units
label has been configured for the value.
∇/∆ arrow display indicates that set-point can be
changed in automatic.
Press ∇ or ∆ to change set-point.
Press the scroll key to display the output in percent on
Line 6.
[OP] appears on Line 5 indicating that Line 6 is
showing the current output value.
∇/∆ arrow display disappears since output cannot be
changed in automatic.