MOD 30ML Operation
SETUP
2-16
Table 8. User Compound Template Configuration (Cont’d)
Step Step Description Line 1 Line 2 Line 6 Entry Description
Millivolt and Thermocouple Inputs Only:
8D14
(TC)
Process Input CJC Source
change value, ENT enters
NXT, PRV change step
PROC INP CJC SRC NONE
NONE, BI AIN 1, S01 TO S11
8D15
(TC)
Process Input Burnout
change value, ENT enters
NXT, PRV change step
PROC INP BURNOUT NONE
NONE - no burnout detection
DN SCALE - signal moves
downscale if burnout is detected.
UP SCALE. - signal moves upscale
if burnout is detected.
All Inputs:
8D16 Process Input Low Quality
change value, ENT enters
NXT, PRV change step
PROC INP LO QUAL -10.0
Result is set BAD if it goes below
this value.
8D17 Process Input High Quality
change value, ENT enters
NXT, PRV change step
PROC INP HI QUAL 110.000
Result is set BAD if it goes above
this value. High quality must be
higher than the low quality value.
8D18 Process Input Quality Alarm
change value, ENT enters
NXT, PRV change step
PROC INP QUAL ALM DISABLE
Disable or Enable.
8D19 Process Input Quality Digital Output
change value, ENT enters
NXT, PRV change step
PROC INP QA D OUT NONE
NONE or S01 to S11 location of
digital output module.
8D20 Process Input Quality Priority
change value, ENT enters
NXT, PRV change step
PROC INP QA PRI 1
0 = suppress unacknowledge
1 to 255 = priority level.
8D21 Process Input (Exit)
moves up to Step 8D
NXT, PRV change step
PROC INP
8E Setpoint (Entry)
moves down to Step 8E1
NXT, PRV change step
CTAG01 SETPT
8E1 Setpoint Display Format
change value, ENT enters
NXT, PRV change step
SETPOINT DISP FMT FLOAT 3
Float 0 = x
Float 1 = x.x
Float 2 = x.xx and so forth to
Float 6 = x.xxxxxx
8E2 Remote Setpoint Input Setup (Entry)
moves down to Step 8E2A
NXT, PRV change step
REMOTE SETPOINT
8E2A Remote Setpoint Slot Position
change value, ENT enters
NXT, PRV change step
REMSETPT SLOT NONE
None, BI AIN 1, BI AIN 2, S01 to
S11
8E2B Remote Setpoint Input Type
change value, ENT enters
NXT, PRV change step
REMSETPT INP TYPE VOLTS
Select type as: VOLTS, MVOLTS,
CURRENT, RESIST, THRMOCPL
1 Slot: RTD2WIRE, CURRNT2W
2 Slots: RTD3WIRE, WIDERES
Built-in only: TC W/CJC, RTD
8E2C Remote Setpoint Input Setup
Same as process value inputs.
See Process Value input setup.
8E2D Remote Setpoint Input Setup (Exit)
moves up to Step 8E2
NXT, PRV change step
REMSETPT