Training Manual
Single Loop Template Lab
3 - 17
3.3.9 Process Input Setup
1 Press NXT PROC INP will be displayed on line 2. We are
entering the process input setup for our PID
control loop.
2 Press DOWN This takes you into the process input definition
menus. SLOT will be displayed on line 2.
3 BI 1 AIN is the default input. We will
accept this.
This is Built-In Analog Input 1. Inputs may be
defined as NONE, BI AIN 1, BI AIN 2 or module
slot S01- to S11- for input being configured
4 Press NXT INP TYPE will be displayed on line 2.
Figure 3 .16.
5 VOLTS is the default for the process
input. Press UP and then ENT to change
this to CURRENT.
Input types may be defined as: VOLTS, MVOLTS,
CURRENT, RESIST, THRMOCPL
1 Slot: RTD2WIRE, CURRNT2W
2 Slots: RTD3WIRE, WIDERES
Built-in only: TC W/CJC, RTD
6 Press NXT until LO SIGNL is displayed
on Line 2
7 Press the DOWN arrow and FST/SLO
keys to change the low signal range to 4
Built-in analog input 1 is wired to a pot in the
demonstration unit which has a range of 0 to 6
Volts
8 Press NXT HI SIGNL is displayed on line 2
9 Use the UP and FST keys to change the
high signal range to 20 and press ENT
10 Press NXT until HI ENGU is displayed
on line 2
11 Use the UP/DOWN keys and the FST Pressing the Up key, will cause the Least
Comentarios a estos manuales