Training Manual
MOD 30ML Operation Lab 2
2 - 8
7 Return to main batch display and
observe step.
8 When controller has entered
HEATUP step, scroll to temperature
control displays (TIC-100 and TIC-
101)
Read the process value of TIC-100.
Refer to the next figure.
Cascade control for temperature is now active
Master controller setpoint value ramps to 111ºF.
This will also ramp to 111 def F in a couple of
minutes
Figure 2 .8.
Master
Temperature
control loop
Note that in MOD 30Ml, continuous control is completely integrated with sequential
control without the need for an external device. Cascade with full tracking provides
tight temperature control.