Training Manual
Single Loop Template Lab
3 - 9
3.3.6 System Compound – Load Defaults:
1 Press NXT until TEMPLATE is displayed
on line 6. See figure below:
2 Press DOWN LOAD DEFAULTS will be displayed on lines 1 and
2. We use the default template as a starting point
for creation of a database. Default values are the
basis for what is shown in the Operation manual.
3 Press DOWN “VERIFY LOAD” will be displayed on lines 1 and
2
Figure 3 .9.
4
Answer YES by pressing DOWN and
ENT
Defaults are the safe or most commonly used
values.
5 Press PRV TEMPLATE is displayed on lines 2 and 6 as
shown in the figure below.
6 Press DOWN EDIT TEMPLATE appears on lines 1 and 2
. There are two types of compounds available in the instrument database. They are:
System Compound and
User Compound.
The System Compound sets some global parameters that will be used by user compounds.
We do not want to make changes to the System compound. We will insert a template for a
User compound and edit it to perform our Flow control loop.
7 Press DOWN CMP LIST *SYSTEM* will be displayed on lines
1 and 2. See the third picture in the figure below.
We are at the System Compound now.