Continuous Control Functions
RAMP SOAK BLOCK
3-9
Field Name Mnemonic Valid Values CWR Data type Attr
Mode
MODE RUN (0)
HOLD (1)
TRK (3)
CWR Short State 30
Mode Quality MODEQ GOOD (0), BAD (1). -WR Discrete 31
Return Mode
RETMODE
RUN (0), HOLD (1) --R Short State 32
Bad Track Input
BADTRK REJECTED (0), ACCEPTED (1). CWR Discrete 33
Process Input
PROCINP The initial local value default is 0.0 CWR Floating pt 34
Track Input
TRKINP Track Input value or source pointer.
The initial local value default is 0.0
CWR Floating pt 35
Track Command
Input
TCMDINP Track Command Input value or source
pointer. If the value is true the mode status will
be TRACK. The initial local value default is
false.
CWR Discrete 36
Reset Input
RESINP NONE, local data or source pointer.
The initial local data value is 0.
CWR Discrete 37
Stop Input
STOPINP NONE, local data or source pointer.
The initial local data value is 0.
CWR Discrete 38
Run Input
RUNINP NONE, local data or source pointer.
The initial local data value is 0.
CWR Discrete 39
Hold Input
HOLDINP NONE, local data or source pointer.
The initial local data value is 0.
CWR Discrete 40
Skip Input
SKIPINP NONE, local data or source pointer.
The initial local data value is 0.
CWR Discrete 41
Segment 1 Target
Value
TVS1 Default value is 0.0 CWR Floating pt 101
...etc 2 through 35 ... ...
Segment 36 Target
Value
TVS36 Default value is 0.0 CWR Floating pt 200
Segment 1 Time
Interval
TIS1 Default value is 0. CWR Msec time 201
...etc 2 through 35 ... ...
Segment 36 Time
Interval
TIS36 Default value is 0. CWR Msec time 300
Segment 1
Guaranteed
GTS1 NO (0), YES (1). Default is NO. CWR Discrete 301
...etc 2 through 35 ... ...
Segment 36
Guaranteed
GTS36 NO (0), YES (1). Default is NO. CWR Discrete 400
Segment 1 State A
SAS1 FALSE (0), TRUE (1). Default is FALSE. CWR Discrete 401
...etc 2 through 35 ... ...
Segment 36 State A
SAS36 FALSE (0), TRUE (1). Default is FALSE. CWR Discrete 500
Segment 1 State B
SBS1 FALSE (0), TRUE (1). Default is FALSE. CWR Discrete 501
...etc 2 through 35 ... ...
Segment 36 State B
SBS36 FALSE (0), TRUE (1). Default is FALSE. CWR Discrete 600
Segment 1 State C
SCS1 FALSE (0), TRUE (1). Default is FALSE. CWR Discrete 601
...etc 2 through 35 ... ...
Segment 36 State C
SCS36 FALSE (0), TRUE (1). Default is FALSE. CWR Discrete 700
Segment 1 State D
SDS1 FALSE (0), TRUE (1). Default is FALSE. CWR Discrete 701
...etc 2 through 35 ... ...
Segment 36 State D
SDS36 FALSE (0), TRUE (1). Default is FALSE. CWR Discrete 800
Vista de pagina 48