Continuous Control Functions
RAMP SOAK BLOCK
3-8
Table 3-1. RSK Block Attributes, Valid Values, Mnemonics, and Data Types
Field Name Mnemonic Valid Values CWR Data type Attr
Version VERSION --R Long State 00
Block Length BLKLEN --R Count 01
State
STATE RUN (0), HOLD (1), OFF (2), DEBUG (3). CWR Short State 02
Bad Inputs
BADINP REJECTED (0), ACCEPTED (1). CWR Discrete 03
Repeat Profile
REPEAT NO (0), YES (1). Default is NO CWR Discrete 04
Use Output States
USE NO (0), YES (1). Default is NO C-R Discrete 05
Startup Type
STYPE START VALUE (0) - Default is START.
TRACK VALUE (1)
PROCESS VALUE (2)
CWR Short State 06
Restart Mode
RESMODE
RUN (0)
HOLD (1)
PREVIOUS (2) Default value is PREVIOUS.
CWR Short State 07
Restart Segment
RESSEG PRESET (0 to 36) or PREVIOUS (255)
Default value is PREVIOUS.
CWR Long State 08
Seg
(Number of Segments)
NUMSEG Value 1 through 36 is allowed. Default is 1. C-R Long State 09
Command CMD The value read from this location will always
be 0. The following values, when written to
this location, will be interpreted as commands:
RESET (1)
STOP (2)
HOLD(3)
RUN(4)
SKIP(5)
-WR Long State 10
Soak Hysteresis
SHYST Valid values are 0.0 or greater. Default is 0.0 CWR Floating pt 11
Ramp Hysteresis
RHYST Valid values are 0.0 or greater. Default is 0.0 CWR Floating pt 12
Start Value
START Default is 0.0 CWR Floating pt 13
Result
R CWR Floating pt 14
Result Quality RQ GOOD (0), BAD (1). -WR Discrete 15
State A
SA CWR Discrete 16
State A Quality SAQ GOOD (0), BAD (1). -WR Discrete 17
State B
SB CWR Discrete 18
State B Quality SBQ GOOD (0), BAD (1). -WR Discrete 19
State C
SC CWR Discrete 20
State C Quality SCQ GOOD (0), BAD (1). -WR Discrete 21
State D
SD CWR Discrete 22
State D Quality SDQ GOOD (0), BAD (1). -WR Discrete 23
Active Segment
Number
ACTSEG Value zero indicates the profile is not active. CWR Long State 24
Active Segment
Number Quality
ACTSEGQ GOOD (0), BAD (1). -WR Discrete 25
Time Remaining
TREM Is the time remaining in a segment. CWR Msec time 26
Time Remaining
Quality
TREMQ GOOD (0), BAD (1). -WR Discrete 27
Cycle Number CYCNUM 0 to 65535. The cycle number stops counting
once the number reaches 65535.
CWR Count 28
Cycle Number Quality
CYCNUMQ
GOOD (0), BAD (1). -WR Discrete 29