Remote I/O Modules Installation Guide for use with 2020N Remote I/O Interface Module
Remote I/O Modules MECHANICAL INSTALLATION 2 MECHANICAL INSTALLATION 2.1 INSTALLATION REQUIREMENTS Read these instructions thoroughly before s
Remote I/O Modules MECHANICAL INSTALLATION 2.2 UNPACKING Unpack and visually inspect modules. Save packing materials for any reshipment, or to su
Remote I/O Modules ELECTRICAL CONNECTIONS 3 ELECTRICAL CONNECTIONS 3.1 CONNECTION GUIDELINES Some installation rules have to be respected. The
Remote I/O Modules ELECTRICAL CONNECTIONS 3.2 POWER CONNECTIONS Supply connections • 24 VDC (process & power supply) 24 VDC (-20%, +25%, i.e
Remote I/O Modules ELECTRICAL CONNECTIONS 3.3 GROUND CONNECTIONS All products in a cabinet must be connected to the same earth. When the remote
Remote I/O Modules ELECTRICAL CONNECTIONS 3.4 REMOTE I/O INTERFACE BUS CONNECTIONS The remote I/O Interface (CS 31) bus is a shield twisted pair
Remote I/O Modules ELECTRICAL CONNECTIONS 3.5 ECZ REMOTE I/O MODULE CARRIER TERMINAL IDENTIFICATION All of the remote I/O units must be mounted
Remote I/O Modules ELECTRICAL CONNECTIONS ECZ Base Switch for Addressing, and Channel Setup The address of a remote I/O module is set by the dip
Remote I/O Modules ELECTRICAL CONNECTIONS 3.6 DIGITAL CONNECTIONS Open Circuit Detection: The following modules require that a 20 to 30 kOhm res
Remote I/O Modules ELECTRICAL CONNECTIONS 3.6.1 ICSI 08 D1 - 8 Non-Isolated 24Vdc Inputs Binary non isolated input unit with 8 input channels f
MicroMod Automation, Inc. The Company MicroMod Automation is dedicated to improving customer efficiency by providing the most cost-effective, applic
Remote I/O Modules ELECTRICAL CONNECTIONS 324I/O REMOTE UNITICSI08D1 24 VDCUnit errorBus errorTEST01234567012314567Input8910111213 14 15Cut Wi
Remote I/O Modules ELECTRICAL CONNECTIONS 3.6.2 ICSI 08 E1: 8 Isolated 24Vdc Inputs Binary isolated input unit with 8 input channels for 24 VDC
Remote I/O Modules ELECTRICAL CONNECTIONS I/O REMOTE UNIT ABB Procontic CS 31Unit errorBus errorTEST012345670 1 2 313 244567InputICSI08E1 12
Remote I/O Modules ELECTRICAL CONNECTIONS 3.6.3 ICSI 08 E3/E4: 8 Isolated 120Vac Inputs Binary isolated input unit with 8 input channels for 12
Remote I/O Modules ELECTRICAL CONNECTIONS ICSI08E3 240 VACI/O REMOTE UNIT ABB Procontic CS 31Unit errorBus errorTEST012345670 1 2 313 244567
Remote I/O Modules ELECTRICAL CONNECTIONS 3.6.4 ICSI 16 D1: 16 Non-Isolated 24Vdc Inputs Binary non isolated input unit with 16 input channels
Remote I/O Modules ELECTRICAL CONNECTIONS • If an external power supply 24 VDC is used for inputs, the "0" VDC must be connected to th
Remote I/O Modules ELECTRICAL CONNECTIONS 3.6.5 ICSI 16 E1: 16 Isolated 24Vdc Inputs Binary isolated input unit with 16 input channels for 24 V
Remote I/O Modules ELECTRICAL CONNECTIONS ICSI16E1 24 VDCI/O REMOTE UNIT ABB Procontic CS 31Unit errorBus errorTEST012345670 1 2 314567Inp
Remote I/O Modules ELECTRICAL CONNECTIONS 3.6.6 ICSO 08 R1: 8 Relay Outputs 2A Binary output unit with 8 relay output channels for 2 A. The uni
Remote I/O Modules CONTENTS CONTENTS Page 1 PRODUCT DESCRIPTION 1.1 OVERVIEW ...
Remote I/O Modules ELECTRICAL CONNECTIONS ICSO08R1 24 VDCI/O REMOTE UNIT ABB Procontic CS 31Unit errorBus errorTEST012345671 2 3132445 670
Remote I/O Modules ELECTRICAL CONNECTIONS 3.6.7 ICSO 08 Y1: 8 Transistor Outputs 24Vdc 2A Binary output unit with 8 transistor output channels
Remote I/O Modules ELECTRICAL CONNECTIONS 324ICSO08Y1 120 VACI/O REMOTE UNIT ABB Procontic CS 31Unit errorBus errorTEST012345671 2 3145 670U
Remote I/O Modules ELECTRICAL CONNECTIONS 3.6.8 ICSK 20 F1: 12 Non-Isolated 24Vdc Inputs & 8 Isolated Relay Outputs Binary input/output uni
Remote I/O Modules ELECTRICAL CONNECTIONS Electrical Connection • The internal 24 VDC (100 mA) power supply is only available for the 230 VAC/12
Remote I/O Modules ELECTRICAL CONNECTIONS Technical Characteristics General Power supply 24 VDC 230 VAC/120 VAC Number of inputs per unit 12
Remote I/O Modules ELECTRICAL CONNECTIONS 3.6.9 ICSC 08 L1: 8 Configurable 24Vdc Inputs or 24Vdc 500mA Transistor Outputs Binary input/output u
Remote I/O Modules ELECTRICAL CONNECTIONS Electrical connection • An external 24 VDC power supply is necessary to use inputs and outputs. Conne
Remote I/O Modules ELECTRICAL CONNECTIONS Technical Characteristics General Power supply 24 VDC 230 VAC/120 VAC Number of inputs per unit 8
Remote I/O Modules INTERNAL DIAGNOSTICS 4 INTERNAL DIAGNOSTICS 4.1 GENERAL All modules execute automatic diagnostic tests which are specific t
Remote I/O Modules CONTENTS ii
Remote I/O Modules INTERNAL DIAGNOSTICS 36
The Company’s policy is one of continuous product improvement and the right is reserved to modify the information
Remote I/O Modules PRODUCT DESCRIPTION 1 PRODUCT DESCRIPTION 1.1 OVERVIEW This document describes the remote I/O module product offering, insta
Remote I/O Modules PRODUCT DESCRIPTION 1.2 BASIC HARDWARE The descriptions included in this section give a brief overview of the functions and fe
Remote I/O Modules PRODUCT DESCRIPTION 1.3 REMOTE I/O MODULES The descriptions included in this section give a brief overview of the functions a
Remote I/O Modules PRODUCT DESCRIPTION 1.4 ELECTROMAGNETIC COMPATIBILITY (EMC) - electrostatic discharge (ESD) according to IEC 801-2 (severity
Remote I/O Modules PRODUCT DESCRIPTION 1.5 RELATED DOCUMENTATION Reference information on the data base structure and configuration parameters fo