Single Loop Process Controller Instruction Manual
Easy-Tune 107
60
Abort EASY-TUNE Switch, L521 was set to 1. EASY-TUNE was aborted.
61
Tuning parameter limits were exceeded and
used in the instrument.
Widen the tuning parameter limits in C385 -
C390 or set Enable Tuning Parameter Limits,
L520 to 0.
Table 11-3. EASY-TUNE Unsuccessful Status Display (Continued)
Step Procedure Suggested Action/Cause/Retry