INSTRUCTION MANUAL Micro-DCI™ Indicator/Totalizer53IT5100APN24479 Rev. 1
Directly beneath the horizontal keypad and concealed behind the front panel pull-down door is the RS-232 Configuration Port. This port provides instr
rollover value. The dropout value specifies a minimum input value required to increment the run-ning total.All of the selectable entries for the Indi
1.2 SCOPE OF BOOKInformation in this book is presented as text, visuals, and tables. All three are required, but thetext has been minimized wherever
Indicator/Totalizer53IT5100 Indicator/TotalizerSection 1IntroductionSection 2Installation
1.3 MODEL NUMBER BREAKDOWNTYPE NO. 53ITSERIES NO. 53IT5100INDICATOR TOTALIZER53IT51 A 2 1 A Engineering File Reference:Power Requirem
1.4 SPECIFICATIONSTable 1-1. SpecificationsItem Specification(s)Power Requirements (as specified) 22 - 26 V dc108 - 132 V rms216 - 264 V rms50/60
Table 1-1. SpecificationsItem Specification(s)Analog Output (ANO0) Signal (is referencedto power common)QuantitySignal RangeLoad RangeAccuracy1 (ANO
Table 1-1. SpecificationsItem Specification(s)Environmental Characteristics (Cont):Transient Immunity (all circuits)EMI SusceptibilityEnclosure Class
Table 1-1. SpecificationsItem Specification(s)Physical CharacteristicsMaterial of Construction:CaseCircuit BoardsBezelDimensionsFlush Panel Mounting
2.0 INSTALLATION2.1 INSPECTIONA list of all items in the shipment is attached to the shipping container. Inspect the equipmentupon arrival for dama
MicroMod Automation, Inc. The Company MicroMod Automation is dedicated to improving customer efficiency by providing the most ost-effective, applica
2.3.2 MOUNTING PROCEDUREFor single and multiple case mounting the instruments are furnished with a trim collar (mountingframe). Figure 2-2 illustrat
Figure 2-1. Outline Dimensions and Panel Cut-Out RequirementsSection 2. Installation2-3
Figure 2-2. Single or Multiple Panel MountingFigure 2-3. Intercase Spacing53IT5100 Indicator/Totalizer2-4
2.4 CONNECTIONS2.4.1 PREPARATORYThe 53IT5100 can be configured for one to four analog inputs (ANI0-3), one analog output (ANO0),two control contact i
2.4.2.1 POWER INPUT (AS SPECIFIED)2.4.2.1.1 DC PowerReference Figure 2-4 and connect the remote 24 V dc power supply to the instrument as follows:1.
2.4.2.3 CONTACT INPUT TO CCI0 AND CCI1Separate contact input signals to CCI0 and CCI1 can be used for alarm inputs. One side of eachremote contact m
Figure 2-4. Controller Rear Power and Signal Terminal Boards53IT5100 Indicator/Totalizer2-8
Figure 2-5. Datalink Installation DiagramSection 2. Installation2-9
3.0 DISPLAYS AND PUSH BUTTONSThis section provides illustrations with item call-outs of the six operator displays, alarm overlays,and engineering mode
Figure 3-2. Dual Bar Graph (Channels 1 & 2)Figure 3-3. Dual Bar Graph (Channels 3 & 4)ANI0 Tag Name (A224)ANI0 Span (C256)50 Segment Graph S
Table of Contents1.0 INTRODUCTION 1-11.1 PRODUCT OVERVIEW . . . . . . . . . . . . . . . . . . . . . . .
Figure 3-4. Quad Process Digital ReadoutFigure 3-5. Quad Totalizer Digital ReadoutANI0 Digital Readout (H000)*ANI1 Digital Readout (H001)*ANI2 Digit
Figure 3-6. Alarm Summary3.2 ALARM OVERLAYAny one of the six operator displays can have the upper quadrant of the display overlaid with anALARM ind
The alarm banner blinking is stopped by pressing the Mode ( ● ) push button on the front panel;the alarm banner remains on the display, but does not b
3.3 FRONT PANEL PUSH BUTTONSThe front panel push buttons are repeated here from Section 1 because they are used in the engi-neering mode display over
3.4 ENGINEERING MODE OVERLAYSThe engineering mode overlays are used to make the necessary parameter entry selections for theoperator displays and to
CONFIGURE Prompt KEY? Prompt A Key Entered on the Edit Line
3.4.2 DISPLAYING A DATAPOINTThe following procedure illustrates how to display the contents of datapoint C175, which is ANI2Alarm Limit 1. Figure 3-
Table 3-3. Procedure to Alter a DatapointStep PressOnceShiftResultPress toLocateTargetChar.Result1●Puts instrument in engineering mode.2If CONFIGUR
3.5 FRONT PANEL PUSH BUTTON ALTERNATIVESThere are four alternative methods other than the front panel push buttons for accessing andchanging database
Figure 3-11. Front Panel Configuration Port Connections53IT5100 Indicator/Totalizer3-12
5.0 MAINTENANCE 5-15.1 SERVICE APPROACH . . . . . . . . . . . . . . . . . . . . . . . . . . .
3.5.1 USING THE HAND HELD CONFIGURERThe Hand Held Configurer (HHC) is a portable terminal designed to interface with the instrumentthrough the config
3.5.1.2 DISPLAYING A DATABASE PARAMETERTo DISPLAY a database parameter, press D and enter the parameter ID, then press ENTER. Thecurrent value of the
3.5.1.4 SETTING OR CHANGING A PASSWORD KEYAs a security feature, the instrument can be configured so that a password key is required to ac-cess the E
2. If F2 is selected, the following menu appears:F2-DATABASEF3-PROGRAM (not applicable)Based on which selection from this menu is made the following o
4.0 CONFIGURATION PARAMETERSThe configuration parameters provide the latitude to define the instrument’s personality attributes,so that while still fu
4.3 CONFIGURING THE DATABASE MODULESThe datapoints in the database modules must be changed to reflect required alterations in the fac-tory standard c
Table 4-3. Analog Input (ANI) ModulePurpose: This module is used to configure input voltage characteristics (e.g., input voltagerange), and how the
Table 4-3. Analog Input (ANI) ModulePurpose: This module is used to configure input voltage characteristics (e.g., input voltagerange), and how the
Table 4-4. Analog Output (ANO) ModulePurpose: The primary purpose of this module is to set the 0 - 20 mA output signal relative to thedisplayed perc
Table 4-5. Contact Input Module (CCI)Purpose: This module allows the action of the CCIs to be reversed (normally a closed contact =1, but can be cha
List of FiguresFigure 1-1. Indicator/Totalizer Operator Displays . . . . . . . . . . . . . . . . . . . 1-2Figu
Table 4-6. Contact Output Module (CCO)Purpose: This module allows the action of the CCOs to be reversed (normally a closed contact =1, but can be ch
Table 4-7. Alarm ModulePurpose: The primary purpose of this module is to set the instrument’s Alarm Index mode, AlarmLimits 1 & 2, and Alarm Dea
Table 4-7. Alarm ModulePurpose: The primary purpose of this module is to set the instrument’s Alarm Index mode, AlarmLimits 1 & 2, and Alarm Dea
Table 4-8. Totalizer ModulePurpose: The totalizers provide a running total of each analog input (ANI0-3). This module isused to set input scaling f
Table 4-8. Totalizer ModulePurpose: The totalizers provide a running total of each analog input (ANI0-3). This module isused to set input scaling f
Table 4-9. Communication ModulePurpose: This module is used to configure the Datalink port parameters (e.g., baud rate, parityselection, etc.). Titl
Table 4-10. System ModulePurpose: This module is used to set the instrument tag name and the display brightness.Title Symbol SystemModuleData-pointD
5.0 MAINTENANCENOTE The factory set calibration constants for ANI0-3 and ANO0 areapplicable only for the main printed circuit board supplied in thepar
After the front display panel is removed, the main printed circuit board can be accessed. The mainprinted circuit board also has the power supply as
5.4 ERROR AND HARDWARE MALFUNCTION MESSAGES •Entire Display Flashes - The watchdog timer has timed out. • CPU RAM FAILURE - IC U1 is bad.•ROM CHKS FA
1.0 INTRODUCTION1.1 PRODUCT OVERVIEWThe 53IT5100 Indicator/Totalizer provides a suite of six operator displays to monitor processactivity for up to
5.6 PARTS LISTThe parts list is provided in Table 5-1 and the parts breakdown is illustrated in Figure 5-1.Table 5-1. Parts ListKey Part Number Desc
Figure 5-1. Illustrated Parts BreakdownSection 5. Maintenance5-5
Figure 5-2. Hand Held Configurer Connector 53IT5100 Indicator/Totalizer5-6
Figure 5-3. Communication ITB Pin AssignmentsSection 5. Maintenance5-7
APPENDIX A: DISCRETE CONTACTOUTPUT CCOsThe discrete output CCOs are not mechanical contact closures but NPN Transistors that are analo-gous to single
Figure A-1. CCO Circuit and its Equivalent Figure A-2. Circuits for Operating DC Relays53IT5100 Indicator/TotalizerA-2
Figure A-3. Operating CCOs in ParallelFigure A-4. CCO with Solid State RelayFigure A-5. CCO Operating CCI DirectlyAppendix A. Discrete Contact Output
APPENDIX B: COMMUNICATIONS B.1 STANDARD COMMUNICATIONSTwo digital communication channels are provided with this instrument: 1) There is a configurat
B.1.1 CONFIGURATIONTo initialize the instrument for binary communications, configure the instrument as described in Ta-ble B-1, Column 3 (Set Up ).T
B.1.2 PROTOCOLThe Datalink protocol requires the host or SUPERVISOR-PC to initiate all transactions. There aretwo basic categories for all of the Da
Figure 1-1. Indicator/Totalizer Operator DisplaysQuad Bar Graph (Chs. 1-4) Dual Bar Graph (Chs. 1&2) Dual Bar Graph (Chs. 3
B.1.3 MESSAGE TYPESThe types of messages that are sent between the host or SUPERVISOR-PC and the Datalink net-work instrument are formatted as follow
B.1.4 COMMUNICATION TRANSACTION EXAMPLES Transaction A Example - Host or SUPERVISOR-PC requests 9 bytes of data beginning at hexa-decimal memory ad
B.1.5 CALCULATING DATA ADDRESSES If communications software must be generated to accommodate unique Datalink applications re-quirements, then the ins
Table B-3. Instrument Memory Address SchemeData TypeBaseMemoryAddressByteSizeData Format Address Calculation AlgorithmH F00H 5 Represents high precis
B.1.6 SOFTWARE CHARACTERISTICS 1. Transparency Rule - whenever 7E hexadecimal is transmitted as anything other thanSOH, a 00 byte will be inserted d
APPENDIX C: DATABASEThe database contains five datapoint types. Each datapoint type represents a specific data format:whole integers, alphanumeric t
Table C-2. DatabaseData-pointTitle Symbol Default Section4TableModuleA008 Unit Tag Name TAG ABB IT5100 4-10 SystemA055 CCI0 Display Message ALARM A 4
Table C-2. DatabaseData-pointTitle Symbol Default Section4TableModuleB340 ALRM1 Alarm Index (ANI1) AIX1 1 4-7 AlarmB345 ALRM2 Alarm Index (ANI2) AIX2
Table C-2. DatabaseData-pointTitle Symbol Default Section4TableModuleH033 Totalizer 1 Actual Total (Display Only) TO1 0 4-8 TotalizerH034 Totalizer 2
Table C-2. DatabaseData-pointTitle Symbol Default Section4TableModuleL440 ANI0 Square Root Signal SQRT0 0 4-3 ANIL441 ANI1 Square Root Signal SQRT1 0
partition, and partitions three and four are occupied by the two contact inputs. All six tag namesfor this display are selectable entries. There are
The Company’s policy is one of continuous product improvement and the rightis reserved to modify the information contained herein without notice, or
Figure 1-2. Indicator/Totalizer Illustrated OverviewRESET HOLE(DEFAULTSDATABASE)PULL-DOWNDOORDISPLAY(96 X 48GASDISCHARGEDOT MATRIX)VERTICAL KEYPAD(6 P
Comentarios a estos manuales