MOD 30ML Data Base Reference
BUILT-IN ANALOG OUTPUT BLOCK
07 Active I/O communications Error (COMMERRA)........................................................... – – R
If the I/O communications error diagnostic is enabled, this active diagnostic status
indicates if the error is active even after acknowledgement. The status can be read
as follows.
YES 1 Diagnostic error is active.
NO 0 Diagnostic error is not active.
08
OUTPUT Error (OUTERRS) .............................................................................................. CWR
The analog output error diagnostic is a status indication for the output circuit error
code (see attribute #12). The diagnostic can be suppressed or enabled as follows.
SUPPRESS 1 Diagnostic error is suppressed. Acknowledgement status remains
clear.
ENABLE 0 Diagnostic error is not suppressed and errors are reported to the
System Event block.
09 Unacked Output Error (OUTERRU) .................................................................................– WR
If the analog output diagnostic error is enabled, this unacknowledged status
indicates if the diagnostic is or is not acknowledged. The status can be
acknowledged or read as follows.
YES 1 Diagnostic error is unacknowledged.
NO 0 Diagnostic error is acknowledged.
10 Active Output Error (OUTERRA) ..................................................................................... – – R
If the analog output diagnostic error is enabled, the active status indicates if the
error is active even after acknowledgement. The status can be read as follows.
YES 1 Diagnostic error is active.
NO 0 Diagnostic error is not active.
11
Output Number (OUTNUM) .............................................................................................. CWR
The analog output number.
1 The analog output is connected to Output 1 of the built-in circuit.
2 The analog output is connected to Output 2 of the built-in circuit.
12 Output Circuit Error (ERROR) .........................................................................................– WR
This error code indicates the reason for report of an Output Error diagnostic
(attribute #08).
0 No error
1 Output too low
2 Output too high