MOD 30ML Functions
DISPLAY INTERFACE BLOCK
Display List
Access to different displays in the display list is controlled locally through the TAG key or
remotely from a count variable input. When a remote display number is present and the value
is less than or equal the number of displays in the list, front face navigation using the TAG
key is disabled and the remote input selects the display.
2.3.2 Display Interface Block Parameters
The mnemonics, valid values, and data types for all fields that may be selected for display
and/or be used in making softwiring connections are listed in Table 2-3. A description of each
attribute is provided in the attribute list which follows the table.
Table 2-3. Display Interface Block Attributes, Valid Values, Mnemonics and Data Types
Field Mnemonic Valid Values CWR Data Type Attr
Version VERSION 1
– – R
Long State 00
Block Length BLKLEN
– – R
Count 01
State
STATE RUN (0)
– – R
Short State 02
Bad Inputs
BADINP Rejected (0), Accepted (1) CWR Discrete 03
DIAGNOSTICS: Group
SUPPGRP NONE, 1 - 7 CWR Long State 04
Faceplate Comm Error
FPCOMS Enabled (0), Suppressed (1). CWR Discrete 05
Faceplate Communication error
unacknowledged
FPCOMU NO (0), YES (1). – WR Discrete 06
Faceplate Communication error
active
FPCOMA NO (0), YES (1).
R
Discrete 07
No Keyboard Response
NOKBDS Enabled (0), Suppressed (1). CWR Discrete 08
No Keybrd Response
unacknowledged
NOKBDU NO (0), YES (1). – WR Discrete 09
No Keybrd Response active NOKBDA NO (0), YES (1).
R
Discrete 10
reserved 11
Faceplate Version FPVER 0.0 - 25.5. – – R Long State 12
Device Tag
DEVTAG CWR Ascii 13
Power Up Display User Tag
PUPDISP DEVICE (0), PREVIOUS (65535)
or display tag
CWR Count 14
Current Display CURDISP – – R Count 15
Current Access Level CURACCS OPERATE (0), TUNE (1),
CONFIGURE (2).
– – R Short State 16
Access Timeout
ACCTIME NONE (0), 1 - 54 minutes. C – – Long State 17
Min Low Alarm Priority
MINLOPRI 2 - 255. C – R Long State 18
Diagnostics: Display Flash
FLSHDIAG NO (0), YES (1). CWR Discrete 19
Diagnostics: Beep
BEEPDIAG NO (0), YES (1). CWR Discrete 20
Diagnostics: Flash/ Beep Rate
DFLSHRAT SLOW (0), FAST (1). CWR Discrete 21
High Priority Process Alarms:
Display Flash
FLSHHIPR NO (0), YES (1). CWR Discrete 22
High Priority Process Alarms:
Beep
BEEPHIPR NO (0), YES (1). CWR Discrete 23
High Priority Process Alarms:
Flash/Beep Rate
HFLSHRAT SLOW (0), FAST (1). CWR Discrete 24
Low Priority Process Alarms:
Display Flash
FLSHLOPR NO (0), YES (1). CWR Discrete 25
Low Priority Process Alarms:
Beep
BEEPLOPR NO (0), YES (1). CWR Discrete 26
Low Priority Process Alarms:
Flash/Beep Rate
LFLSHRAT SLOW (0), FAST (1). CWR Discrete 27
Table 2-3. Display Interface Block Attributes, Valid Values, Mnemonics and Data Types (Cont’d)
2-26