MOD 30ML Functions
CONFIGURATION EXAMPLES
Figure 3. 21.
PID Block Properties
The PID block has the most extensive configuration. Select the Setpoint tab in the PID bloc
configuration and change the Setpoint Limits – High to 200 also to match the process
variable range.
We wont be making any other changes to the PID block in this tutorial.
Click on the OK block to accept the changes made tot his block.
The compound has a display block configured to show the proves variable, setpoint, output,
output mode and setpoint mode from the PID block. This display block is configured with the
process variable and setpoint range as 0-100. We need to change this to 0-200 to match the
changes we did in the VCI and the PID blocks.
Open this Display block (DISP) by double-clicking on it. Click on the Formats tab of the
display block configuration.