Micromod MOD: Remote I/O Modules for use with 2020N Remote Manual de usuario Pagina 20

  • Descarga
  • Añadir a mis manuales
  • Imprimir
  • Pagina
    / 42
  • Tabla de contenidos
  • MARCADORES
  • Valorado. / 5. Basado en revisión del cliente
Vista de pagina 19
Remote I/O Modules
ELECTRICAL CONNECTIONS
324
I/O REMOTE UNIT
ICSI08D1 24 VDC
Unit error
Bus error
TEST
0
1
2
3
4
5
6
7
0
1
2
3
1
4
56
7
Input
8
9
10
11
12
13 14 15
Cut Wire
ABB Procontic CS 31
Shield
Bus # 1
Bus # 2
Ground
Common +
Common -
Common -
A
B
C
D
E
F
G
H
Common +
Common +
Common +
Common +
Common +
Not to
be used
Not to
be used
Not to
be used
Technical Characteristics:
Power supply 24 VDC 230 or 120 VAC 50 or 60 Hz
Number of inputs per unit 8 8
Power supply isolation no yes (1500 VAC)
Inputs opto-isolated no no
Supply output regulated 24 VDC (± 5 %) - 100 mA
Signal level of the input, nominal value 24 VDC 24 VDC
Signal level of the input :
0 - OFF signal –3 to +5V –3 to +5V
1 - ON signal +15 to +30V +15 to +30V
Open circuit detection* yes yes
Input current for 24 VDC 6 mA 6 mA
Input delay 8 ms 8 ms
Maximum power consumption 0.2 A 10 VA
Maximum power dissipation 4.5 W 8 W
* A 20 to 30 kOhm resistor must be mounted in parallel of each input captor to get open
circuit detection for that channel. With an inductive captor, the minimal current is 1 mA.