53SL5100B Single-Loop Controller
INSTRUCTION MANUAL
31
Table 4-7. Contact Output Module (CCO)
Purpose: This module allows the action of the CCO to be reversed (normally a closed contact = 1, but can be
changed to = 0).
Title Symbol Data-point Default Attribute
Contact
Output
(Display
Only)
CCO L024 0
If CCO = 0 and OINV = 0, then it is open.
If CCO = 0 and OINV = 1, then it is closed.
If CCO = 1 and OINV = 0, then it is closed.
If CCO = 1 and OINV = 1, then it is open.
Contact
Output
Invert
OINV L288 0
As shown above, it reverses the action of the
CCO datapoint.
Tag
Name
COTAG0
COTAG1
A280
A281
CCO-0
CCO-1
An assignable 10 character name for the
contact control output.
Figure 4-3. CCI0 Figure 4-4. CCO0
NOTES:
WD = Watchdog
These figures are graphical representations of the signal conditioning that occurs on the
instrument main board. They are provided for reference purposes only.