CUSTOMIZATION GUIDEMulti-Loop Process Controller53MC5000MICRO-DCI MODULAR CONTROLLERPN24975ARev. 1

Pagina 2 - MicroMod Automation, Inc

these values are double and standard character sets (B09 = 0,1) are mapped to large charactersets. The DFC atom is forced to active prior to each exe

Pagina 3 - Table of Contents

F-CIM 104MATH ENOT REUSABLEFunction:CSn0Sn-11C88 * Sn-1 + C892C88 * Sn-1 + C89 * A + C90 * B3C88 * Sn-1 * A * B + C894 C88∗Sn−1A + C89*B5C88 * Sn-1 +

Pagina 4 - List of Tables

F-CIM 105MATH FNOT REUSABLEFunction:CSn0Sn-11C91 * Sn-1 + C922C91 * Sn-1 + C92 * A + C93 * B3C91 * Sn-1 * A * B + C924 C91∗Sn−1A + C92*B5C91 * Sn-1 +

Pagina 5 - READ FIRST

F-CIM 106MATH GNOT REUSABLEFunction:CSn0Sn-11C94 * Sn-1 + C952C94 * Sn-1 + C95 * A + C96 * B3C94 * Sn-1 * A * B + C954 C94∗Sn−1A + C95*B5C94 * Sn-1 +

Pagina 6 - 1.1 Description

F-CIM 107MATH HNOT REUSABLEFunction:CSn0Sn-11C97 * Sn-1 + C982C97 * Sn-1 + C98 * A + C99 * B3C97 * Sn-1 * A * B + C984 C97∗Sn−1A + C98*B5C97 * Sn-1 +

Pagina 7

3.4 Custom F-CIM ModuleA custom F-CIM module is a custom F-TRAN subroutine which follows specific rules. The user canwrite either reusable or non-reus

Pagina 8 - 2.0 F-TRAN PROGRAMMING

\F-CIM CUSTOM200\\NON-REUSABLE\\INPUTS\\X PV\\A REMOTE SP\\B FEEDFORWARD\\C REMOTE ENA\C100 = C255C120 = F*253C122 = F*254L115 = F*255L123 = L107C127

Pagina 9 - 2.2 Types of Programs

3.5 F-CIM Example1: Define the process control function to be implemented:Produce a single loop PID controller with output tracking on closure of cont

Pagina 10 - 2.4 The F-TRAN Language

5: Enter the function block input values and parameters into the database. The methods for enteringparameters are described in IB53MC5000 section 3.4.

Pagina 11

Figure 3-3. Example of Function Block Diagram(The referenced I/O modules are shown in addition to the programdiagram, for user’s convenience.)MODULAR

Pagina 12 - 2.4.3 Operators

[ THIS PAGE LEFT INTENTIONALLY BLANK ]MODULAR CONTROLLER CUSTOMIZATION GUIDE3-57

Pagina 13

The system operands are assigned symbols which may represent abbreviations for input or outputsignals, displays, parameters, etc. These symbols are ea

Pagina 14

Figure 3-4a. F-CIM OverviewMODULAR CONTROLLER CUSTOMIZATION GUIDE3-58

Pagina 15

Figure 3-4b. F-CIM OverviewMODULAR CONTROLLER CUSTOMIZATION GUIDE3-59

Pagina 16

Figure 3-5a. Database Modules OverviewRefer to Instruction Bulletin 53MC5000 Section 4.1MODULAR CONTROLLER CUSTOMIZATION GUIDE3-60

Pagina 17

Figure 3-5b. Database Modules OverviewRefer to Instruction Bulletin 53MC5000 Section 4.1MODULAR CONTROLLER CUSTOMIZATION GUIDE3-61

Pagina 18

MODULAR CONTROLLER CUSTOMIZATION GUIDE3-62

Pagina 19 - 2.4.5.1 Assignment Statements

MODULAR CONTROLLER CUSTOMIZATION GUIDE3-63

Pagina 20

APPENDIX 0CHARACTER SET 0Character Set 0 is applicable to PRINTn display statement found in Section 2.4.5.11.MODULAR CONTROLLER CUSTOMIZATION GUIDEApp

Pagina 21

MODULAR CONTROLLER CUSTOMIZATION GUIDEAppendix 0 - 2

Pagina 22

MODULAR CONTROLLER CUSTOMIZATION GUIDEAppendix 0 - 3

Pagina 23 - 2.4.5.4 IF-ELSE Statements

MODULAR CONTROLLER CUSTOMIZATION GUIDEAppendix 0 - 4

Pagina 24 - 2.4.5.6 Case Statements

2.4.2 OperandsWhen writing programs for the Controller it is important to remember that the permissible operandsinclude all the various elements descr

Pagina 25 - 2.4.5.11 Display Statements

APPENDIX 1CHARACTER SET 1Character Set 1 is applicable to PRINTn display statement found in Section 2.4.5.11.MODULAR CONTROLLER CUSTOMIZATION GUIDEApp

Pagina 26

MODULAR CONTROLLER CUSTOMIZATION GUIDEAppendix 1 - 2

Pagina 27

MODULAR CONTROLLER CUSTOMIZATION GUIDEAppendix 1 - 3

Pagina 28

The Company’s policy is one of continuous product improvement and the rightis reserved to modify the information contained herein without notice, or

Pagina 29 - 2.5 Subroutine Library

TABLE 1. F-TRAN OPERATORSOPERATORFUNCTIONSTYPE"L" "B" "C" "H"Add +++Subtract ---Multiply * * *Divide ///Square

Pagina 30

Operators + - * / These operators may be used to effect addition,subtraction, multiplicationor division operations. The respective operator performs

Pagina 31

The following data transformations are allowable and may be used as required in programs. Theseoperators are often required in computations involving

Pagina 32

W and D OperatorsThe swap (W) and duplicate (D) operators may be used to swap and duplicate data values of the same type. For example, when a D operat

Pagina 33

logical "1" = skip "n" lines logical "0" = no skip| OperatorThe absolute value operator will replace the top value on th

Pagina 34

Data Type Positions RequiredL and B 1 C 3 H 5 A 10 F 5F-TRAN s

Pagina 35

“+” 5) Remove and add the top two values in the stack and place resulting sum back in the stack (level 1), leaving (level 2) clear. 6) End of s

Pagina 36

MicroMod Automation, Inc. The Company MicroMod Automation is dedicated to improving customer efficiency by providing the most ost-effective, applica

Pagina 37

2.4.5.2 Comparison Statements Two typical data comparison statements are given below. In the 2nd statement, the logical resultsof the two comparisons

Pagina 38

“:” 9) Removes and compares the top two data values from the stack memory. If the value of “C06” is greater than or equal to “C23 H05 $ *”, the

Pagina 39

The stack memory will operate as follows:“C02” 1) Places the value of C02 in stack memory (level 1). “Z” 2) Removes the value on the top of the stac

Pagina 40

If the value of C00 is greater than or equal to the value of C01, a logical “1” is placed in the stackmemory. A skip will be executed only if the bit

Pagina 41

2.4.5.5 WHILE StatementWhen it is necessary to have an operation execute repeatedly while a particular condition is true(i.e., = 1). the condition, in

Pagina 42

2.4.5.7 Unconditional Jump Statements JxxxThe unconditional jump statement is used to control the transfer of operations from one point to an-other in

Pagina 43

VBARVBAR <height> <max. height> <width>This function draws a vertical bargraph at the current x, y coordinates.Height is the actual

Pagina 44

INPUTINPUT <string expression>This command transfers the value of the datapoint specified by the string expression tothe engineering mode modify

Pagina 45

VTRENDVTREND <0-7>This command draws the designated trend. It locates the origin of the plot at "0",cursor "y". The time lin

Pagina 46

2.5 Subroutine LibraryG00 - Setpoint Generator-0G01 - Setpoint Generator-1G02 - Setpoint Generator-2G03 - Setpoint Generator-3G04 - Deviation/Alarm Ca

Pagina 47 - 2.6 F-TRAN Program Capacity

Table of Contents1.0 Introduction To Customization. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-11.1 Description . .

Pagina 48

G00 SETPOINT GENERATOR - 0 NAME SYMBOL DATAPOINT INPUTS REMOTE SETPOINT RSP0 C120 REMOTE SP ENABLE RE0 L115 SETPOINT TRACK INPUT STV0 C128 SETPO

Pagina 49

G01SETPOINT GENERATOR - 1 NAME SYMBOL DATAPOINT INPUTS REMOTE SETPOINT RSP1 C156 REMOTE SP ENABLE RE1 L139 SETPOINT TRACK INPUT STV1 C164 SETPO

Pagina 50 - 2.7.4 IF Statements

G02 SETPOINT GENERATOR - 2 NAME SYMBOL DATAPOINT INPUTS REMOTE SETPOINT RSP2 C192 REMOTE SP ENABLE RE2 L163 SETPOINT TRACK INPUT STV2 C200 SETPO

Pagina 51 - 2.7.6 Case Statements

G03 SETPOINT GENERATOR - 3 NAME SYMBOL DATAPOINT INPUTS REMOTE SETPOINT RSP3 C228 REMOTE SP ENABLE RE3 L187 SETPOINT TRACK INPUT STV3 C236 SET

Pagina 52 - 2.8 A Programming Example

G04DEVIATION/ALARM CALCULATION - 0INPUTS NAME SYMBOL DATAPOINTSETPOINT SP0 C101PROCESS VARIABLE PV0 C100PARAMETERS SETPOINT SLEW RATE T10 C117CONTROL

Pagina 53

G05DEVIATION/ALARM CALCULATION - 1INPUTS NAME SYMBOL DATAPOINTSETPOINT SP1 C137PROCESS VARIABLE PV1 C136PARAMETERS SETPOINT SLEW RATE T11 C153CONTROL

Pagina 54 - 3.2 Module Library (

G06DEVIATION/ALARM CALCULATION - 2INPUTS NAME SYMBOL DATAPOINTSETPOINT SP2 C173PROCESS VARIABLE PV2 C172PARAMETERS SETPOINT SLEW RATE T12 C189CONTROL

Pagina 55 - 3.3.3 Building Steps

G07DEVIATION/ALARM CALCULATION - 3INPUTS NAME SYMBOL DATAPOINTSETPOINT SP3 C209PROCESS VARIABLE PV3 C208PARAMETERS SETPOINT SLEW RATE T13 C225CONTROL

Pagina 56 - Figure 3-1. Configuring F-CIM

G08PID - 0NAME SYMBOL DATAPOINTINPUTSPROCESS VARIABLE PV0 C100DEVIATION DV0 C121RESET FEEDBACK RF0 C127CONTROL TRACK COMMANDCTC0 L123PARAMETERS PROPO

Pagina 57 - Figure 3-2. F-CIM Directory

G09PID - 1NAME SYMBOL DATAPOINTINPUTSPROCESS VARIABLE PV1 C136DEVIATION DV1 C157RESET FEEDBACK RF1 C163CONTROL TRACK COMMANDCTC1 L147PARAMETERS PROPO

Pagina 58

3.0 F-CIM (CONTROL INTERCONNECTION MODULES) . . . . . . . . . . . . . . . . . . . . . 3-13.1 Configuring a F-CIM sequence . . . . . . . . . . . . . .

Pagina 59 - NOT REUSABLE

G10PID - 2NAME SYMBOL DATAPOINTINPUTSPROCESS VARIABLE PV2 C172DEVIATION DV2 C193RESET FEEDBACK RF2 C199CONTROL TRACK COMMANDCTC2 L171PARAMETERS PROPO

Pagina 60 - F-CIM 41

G11PID - 3NAME SYMBOL DATAPOINTINPUTSPROCESS VARIABLE PV3 C208DEVIATION DV3 C229RESET FEEDBACK RF3 C235CONTROL TRACK COMMANDCTC3 L195PARAMETERS PROPO

Pagina 61

G12AUTO/MANUAL SWITCH - 0INPUTS NAME SYMBOL DATAPOINTCONTROL OUTPUT CO0 C123AUTO ENABLE AE0 L114OUTPUT TRACK VALVE OTV0 C129OUTPUT TRACK SWITCH SWOTV0

Pagina 62 - SETPOINT GENERATOR - 0

G13AUTO/MANUAL SWITCH - 1INPUTS NAME SYMBOL DATAPOINTCONTROL OUTPUT CO1 C159AUTO ENABLE AE1 L138OUTPUT TRACK VALVE OTV1 C165OUTPUT TRACK SWITCH SWOTV1

Pagina 63

G14AUTO/MANUAL SWITCH - 2INPUTS NAME SYMBOL DATAPOINTCONTROL OUTPUT CO2 C195AUTO ENABLE AE2 L162OUTPUT TRACK VALVE OTV2 C201OUTPUT TRACK SWITCH SWOTV2

Pagina 64 - F-CIM 51

G15AUTO/MANUAL SWITCH - 3INPUTS NAME SYMBOL DATAPOINTCONTROL OUTPUT CO3 C231AUTO ENABLE AE3 L186OUTPUT TRACK VALVE OTV3 C237OUTPUT TRACK SWITCH SWOTV3

Pagina 65 - EXTENDED MATH A

G22DISPLAY HANDLERPARAMETERS NAME SYMBOL DATAPOINTNUMBER OF DISPLAYGROUPSMDG B17NUMBER OFSCREENS/GROUPMDS B18CURRENT DISPLAY CDP B19CURRENT DISPLAY ST

Pagina 66

2.6 F-TRAN Program Capacity Program capacity has two aspects. It refers to that portion of non-volatile memory which can beloaded with; Control F-TRAN

Pagina 67

A user friendly interface for performing these activities is provide in the 53SU5000 SUPERVISOR-PCand 53HC3300C CUSTOM PROGRAM INTERFACE Instruction B

Pagina 68

2.7 Summary, F-TRAN Instruction SetLEGENDS: Symbols used in this discussion.< >Used to enclose an expression | Separates possible alternat

Pagina 69

READ FIRSTWARNINGINSTRUCTION MANUALSDo not install, maintain, or operate this equipment without reading, understanding andfollowing the proper MicroMo

Pagina 70 - EXTENDED MATH B

2.7.1 Statements Composed of operands and expressions2.7.2 Assignment StatementsNOTE: In cases where the right side of the statement is a different ty

Pagina 71

2.7.5 While StatementsWHILE < logical expression > { }2.7.6 Case StatementsCASESOF < B operand >CASE { }CASE

Pagina 72

2.8 A Programming ExampleThe following is a program text file that illustrates the use of the F-TRAN language in building asimple single loop controll

Pagina 73

3.0 F-CIM (CONTROL INTERCONNECTION MODULES)Control Interconnection Modules provide a method of customizing the 53MC5000 (Extended Func-tionality) cont

Pagina 74

3.1 Configuring a F-CIM sequenceF-CIM sequences can be configured using four different methods:1. From the controller’s front panel using the procedur

Pagina 75

3.3.2 Erasing StepsSelecting ERASE (pressing F3 when ERASE is displayed) causes the following line to appear:n SURE? YPressing F1 (i.e., selecting NO

Pagina 76

Figure 3-1. Configuring F-CIMMODULAR CONTROLLER CUSTOMIZATION GUIDE3-4

Pagina 77

F-CIM Sn-1 AIN BIN CIN TYPEADDSUBMULDIVSQRTLOG2YPOWXABSLINVLANDLORLXORWRITEREADAx+ B SWITCHCOMPJ - KSP0PID0AM0DEV0SP1PID1

Pagina 78

[ THIS PAGE LEFT INTENTIONALLY BLANK ]MODULAR CONTROLLER CUSTOMIZATION GUIDE3-6

Pagina 79

F-CIM 22DISPLAY HANDLERNOT REUSABLEPARAMETERS NAME SYMBOL DATAPOINTNUMBER OF DISPLAYGROUPSMDG B17NUMBER OFSCREENS/GROUPMDS B18CURRENT DISPLAY CDP B19C

Pagina 80

1.0 INTRODUCTION TO CUSTOMIZATION1.1 DescriptionThe MicroMod Automation MICRO-DCI® 53MC5000 PCS is a microprocessor based controllerthat can be easil

Pagina 81

F-CIM 41PID - 0NOT REUSABLENAME SYMBOL DATAPOINTINPUTSSn-1DEVIATION DV0 C121A [unused]B RESET FEEDBACK RF0 C127C CONTROL TRACK COM-MANDCTC0 L123PARAM

Pagina 82 - REUSABLE

F-CIM 43AUTO/MANUAL SWITCH - 0NOT REUSABLEINPUTS NAME SYMBOL DATAPOINTSn-1CONTROL OUTPUT CO0 C123A AUTO ENABLE AE0 L114B OUTPUT TRACK VALVE OTV0 C129C

Pagina 83

F-CIM 44SETPOINT GENERATOR - 0NOT REUSABLENAME SYMBOL DATAPOINTINPUTSSn-1REMOTE SETPOINT RSP0 C120A REMOTE SP ENABLE RE0 L115B SETPOINT TRACK INPUT ST

Pagina 84

F-CIM 47DEVIATION/ALARM CALCULATION - 0NOT REUSABLEINPUTS NAME SYMBOL DATAPOINTSn-1SETPOINT SP0 C101A PROCESS VARIABLE PV0 C100PARAMETERS SETPOINT SLE

Pagina 85

F-CIM 51PID - 1NOT REUSABLENAME SYMBOL DATAPOINTINPUTSSn-1DEVIATION DV1 C157A [unused]B RESET FEEDBACK RF1 C163C CONTROL TRACK COM-MANDCTC1 L147PARAM

Pagina 86

F-CIM 52EXTENDED MATH ANOT REUSABLEFunction:CSn0Sn-11 C354 * Sn-1 + C3552 C354 * Sn-1 + C355 * A + C356 * B3 C354 * Sn-1 * A * B + C3554 C354∗Sn−1A +

Pagina 87

F-CIM 53AUTO/MANUAL SWITCH - 1NOT REUSABLEINPUTS NAME SYMBOL DATAPOINTSn-1CONTROL OUTPUT CO1 C159A AUTO ENABLE AE1 L138B OUTPUT TRACK VALVE OTV1 C165C

Pagina 88

F-CIM 54SETPOINT GENERATOR - 1 NOT REUSABLENAME SYMBOL DATAPOINT INPUTS Sn-1REMOTE SETPOINT RSP1 C156 A REMOTE SP ENABLE RE1 L139 B SETPOINT TRACK

Pagina 89

F-CIM 57DEVIATION/ALARM CALCULATION - 1NOT REUSABLEINPUTS NAME SYMBOL DATAPOINTSn-1SETPOINT SP1 C137A PROCESS VARIABLE PV1 C136PARAMETERS SETPOINT SLE

Pagina 90

F-CIM 61PID - 2NOT REUSABLENAME SYMBOL DATAPOINTINPUTSSn-1DEVIATION DV2 C193A [unused]B RESET FEEDBACK RF2 C199C CONTROL TRACK COM-MANDCTC2 L171PARAM

Pagina 91

FIGURE 1-1. Modular Controller Front PanelNote: EMODE = Engineering ModeMODULAR CONTROLLER CUSTOMIZATION GUIDE1-2

Pagina 92

F-CIM 62EXTENDED MATH BNOT REUSABLEFunction:CSn0Sn-11 C366 * Sn-1 + C3672 C366 * Sn-1 + C367 * A + C368 * B3 C366 * Sn-1 * A * B + C3674 C366∗Sn−1A +

Pagina 93

F-CIM 63AUTO/MANUAL SWITCH - 2NOT REUSABLEINPUTS NAME SYMBOL DATAPOINTSn-1CONTROL OUTPUT CO2 C195A AUTO ENABLE AE2 L162B OUTPUT TRACK VALVE OTV2 C201C

Pagina 94

F-CIM 64SETPOINT GENERATOR - 2NOT REUSABLENAME SYMBOL DATAPOINTINPUTS Sn-1REMOTE SETPOINT RSP2 C192A REMOTE SP ENABLE RE2 L163B SETPOINT TRACK INPUT S

Pagina 95

F-CIM 67DEVIATION/ALARM CALCULATION - 2NOT REUSABLEINPUTS NAME SYMBOL DATAPOINTSn-1SETPOINT SP2 C173A PROCESS VARIABLE PV2 C172PARAMETERS SETPOINT SLE

Pagina 96 - F-CIM 100

F-CIM 71PID - 3NOT REUSABLENAME SYMBOL DATAPOINTINPUTSSn-1DEVIATION DV3 C229A [unused]B RESET FEEDBACK RF3 C235C CONTROL TRACK COM-MANDCTC3 L195PARAM

Pagina 97 - F-CIM 101

F-CIM 73AUTO/MANUAL SWITCH - 3NOT REUSABLEINPUTS NAME SYMBOL DATAPOINTSn-1CONTROL OUTPUT CO3 C231A AUTO ENABLE AE3 L186B OUTPUT TRACK VALVE OTV3 C237C

Pagina 98 - F-CIM 102

F-CIM 74SETPOINT GENERATOR - 3NOT REUSABLENAME SYMBOL DATAPOINTINPUTS Sn-1REMOTE SETPOINT RSP3 C228A REMOTE SP ENABLE RE3 L187B SETPOINT TRACK INPUT S

Pagina 99 - F-CIM 103

F-CIM 77DEVIATION/ALARM CALCULATION - 3NOT REUSABLEINPUTS NAME SYMBOL DATAPOINTSn-1SETPOINT SP3 C209A PROCESS VARIABLE PV3 C208PARAMETERS SETPOINT SLE

Pagina 100 - Description:

F-CIM 82J-K LATCHREUSABLEFunction:IF Sn-1 < 1.0 & A< 1.0Sn = SnIF Sn-1 ≥1 & A ≥1 Sn = not SnIF Sn-1 ≥1 & A <1.0 Sn = 1.0

Pagina 101 - F-CIM 105

F-CIM 83COMPARITORREUSABLEFunction:IF Sn-1 ≥A or Sn-1 ≤B Sn = 1IF A-C 1≥Sn-1 or B + C ≥Sn-1Sn = 0Description:This function acts as a comp

Pagina 102 - F-CIM 106

2.0 F-TRAN PROGRAMMING2.1 DescriptionAn F-TRAN program is written as a sequence of language statements combined with necessarysystem routines to adapt

Pagina 103 - F-CIM 107

F-CIM 84SWITCHREUSABLEFunction:IF B ≥1 Sn = AELSE Sn = Sn-1Description:If the B input is greater than or equal to 1.0, the result of this modul

Pagina 104 - 3.4 Custom F-CIM Module

F-CIM 85AX + BREUSABLEFunction:Sn = A * Sn-1 + BDescription:The result of this module is a linear scaling of the result of the previous step.A and B

Pagina 105

F-CIM 86READ REUSABLEFunction:Sn = ADescription:The READ module copies any L, B, C[S], or H data base parameter into the step result.MODULAR CONTROLLE

Pagina 106 - 3.5 F-CIM Example

F-CIM 87WRITE REUSABLEFunction:IF B ≥ 1 A = Sn-1 Sn = Sn-1Description:The WRITE module copies the result of the previous step to data base parame

Pagina 107

F-CIM 88LOGICAL EXCLUSIVE OR REUSABLEFunction:IF Sn-1 ≥ 1 and A < 1 Sn = 1.0 IF Sn-1< 1 and A ≥ 1 Sn = 1.0 ELSE

Pagina 108

F-CIM 89LOGICAL OR REUSABLEFunction:IF (Sn-1 ≥ 1 or A ≥ 1) Sn = 1.0 ELSE Sn = 0.0Description:This module p

Pagina 109

F-CIM 90LOGICAL AND REUSABLEFunction:IF (Sn-1 ≥ 1 and A ≥ 1) Sn = 1.0 ELSE Sn = 0.0Description:This mod

Pagina 110 - Figure 3-4a. F-CIM Overview

F-CIM 91LOGICAL INVERTREUSABLEFunction:IF Sn-1 ≥ 1 Sn = 0ELSE Sn = 1Description:This module produces an output of 0.0 if t

Pagina 111 - Figure 3-4b. F-CIM Overview

F-CIM 92ABSOLUTE VALUEREUSABLEFunction:Sn = | Sn-1|Description:This module produces an output with the same magnitude as the A input, but with a posit

Pagina 112

F-CIM 93EXPONENTIALREUSABLEFunction:Sn = ABDescription:The output of this module is the value of A raised to the power specified by the B input. Both

Pagina 113

2.2 Types of ProgramsUnlike other MICRO-DCI instruments, the 53MC5000 Controller supports several types of F-TRANprograms.2.2.1 Control F-TRAN These p

Pagina 114

F-CIM 94LOG BASE TWOREUSABLEFunction:Sn = lg2 (Sn-1)Description:The output of this module is the base two logarithm of the output of the previous ste

Pagina 115

F-CIM 95SQUARE ROOTREUSABLEFunction:Sn = Sn-1Description:The output of this module is the square root of the output of the previous step.MODULAR CON

Pagina 116 - APPENDIX 0

F-CIM 96TWO INPUT DIVIDERREUSABLEFunction:Sn = A/BDescription:The output of this module is the quotient of the A input divided by the B input. The A a

Pagina 117 - Appendix 0 - 2

F-CIM 97TWO INPUT MULTIPLIERREUSABLEFunction:Sn = Sn-1 x ADescription:The output of this module is the product of the A input and the output of the pr

Pagina 118 - Appendix 0 - 3

F-CIM 98TWO INPUT SUBTRACTORREUSABLEFunction:Sn = A - BDescription:The output of this module is the difference of the A input minus the B input. The A

Pagina 119 - Appendix 0 - 4

F-CIM 99TWO INPUT ADDERREUSABLEFunction:Sn = Sn-1 + ADescription:The output of this module is the sum of the A input and the output of the previous st

Pagina 120 - APPENDIX 1

F-CIM 100MATH ANOT REUSABLEFunction:CSn0Sn-11C76 * Sn-1 + C772C76 * Sn-1 + C77 * A + C78 * B3C76 * Sn-1 * A * B + C774 C76∗Sn−1A + C77*B5C76 * Sn-1 +

Pagina 121 - Appendix 1 - 2

F-CIM 101MATH BNOT REUSABLEFunction:CSn0Sn-11C79 * Sn-1 + C802C79 * Sn-1 + C80 * A + C81 * B3C79 * Sn-1 * A * B + C804 C79∗Sn−1A + C80*B5C79 * Sn-1 +

Pagina 122 - Appendix 1 - 3

F-CIM 102MATH CNOT REUSABLEFunction:CSn0Sn-11C82 * Sn-1 + C832C82 * Sn-1 + C83 * A + C84 * B3C82 * Sn-1 * A * B + C834 C82∗Sn−1A + C83*B5C82 * Sn-1 +

Pagina 123

F-CIM 103MATH DNOT REUSABLEFunction:CSn0Sn-11C85 * Sn-1 + C862C85 * Sn-1 + C86 * A + C87 * B3C85 * Sn-1 * A * B + C864 C85∗Sn−1A + C86*B5C85 * Sn-1 +