Logic Functions
FC OUTPUT FC OUTPUT
0A4A OR NOT B
1 A OR B 5 A AND NOT B
2 A AND B 6 J-K LATCH
3 A XOR B 7 D LATCH
Invert output if FC = FC + 128
Expanded Logic Functions
INPUTS OUTPUT INPUTS INVERTED OUTPUT
FC A B A FC A B A
0 0 1 0 128 0 1 1
0 1 1 1 128 1 1 0
0 0 0 0 128 0 0 1
0 1 0 1 128 1 0 0
FC A B A OR B FC A B A OR B
1 0 1 1 129 0 1 0
1 1 1 1 129 1 1 0
1 0 0 0 129 0 0 1
1 1 0 1 129 1 0 0
FC A B A AND B FC A B A AND B
2 0 1 0 130 0 1 1
2 1 1 1 130 1 1 0
2 0 0 0 130 0 0 1
2 1 0 0 130 1 0 1
FC A B A XOR B FC A B A XOR B
3 0 1 1 131 0 1 0
3 1 1 0 131 1 1 1
3 0 0 0 131 0 0 1
3 1 0 1 131 1 0 0
FC A B A OR NOT B FC A B A OR NOT B
4 0 1 0 132 0 1 1
4 1 1 1 132 1 1 0
4 0 0 1 132 0 0 0
4 1 0 1 132 1 0 0
FC A B A AND NOT B FC A B A AND NOT B
5 0 1 0 133 0 1 1
5 1 1 0 133 1 1 1
5 0 0 0 133 0 0 1
5 1 0 1 133 1 0 0
FC A B JK LATCH FC A B JK LATCH
6 0 1 0 134 0 1 1
6 1 1 opposite last value 134 1 1 opposite last value
6 0 0 unchanged 134 0 0 unchanged
6 1 0 1 134 1 0 0
FC A B D LATCH FC A B D LATCH
7 0 1 0 135 0 1 1
7 1 1 1 135 1 1 0
7 0 0 unchanged 135 0 0 unchanged
7 1 0 unchanged 135 1 0 unchanged
Unchanged
means the value from the last execution is used.
Opposite last value
means the opposite of the value from the last
execution is used.