3.2.5 CONFIGURE A MODULE
The navigational sequence would be the following
:
Select Module Type (then Module, if theres more than one Module)
Select Page (Skipped when theres only a single page)
Select Parameter
3.2.5.1 Module-Mode ConfigurationProcedure
Press the
Mode
button to enter ENGINEER mode
indicated by the appearance of either
CONFIGURE
,
DISPLAY
or
PROGRAM
at the bottom of the display..
If
CONFIGURE
does not appear, press F2 until
CON-
FIGURE
appears at the bottom of the display.
When
CONFIGURE
is displayed, press F3 to enter the
CONFIGURE
mode.
For a Hi-Res display, as shown, press F2 until
MOD-
ULE
appears at the bottom of the display.
When
MODULE
is displayed, press F3 to enter the
MODULE
mode.
The screen should now appear as shown on the right.
Select the desired MODULE type to be configured by
using the keys to navigate to the desired mod-
ule type.
In this example, the button was used to navigate to
the
CONTROL
module type as shown to the right.
Press F3 to select this Module type.
MODULAR CONTROLLER QUICK START
3-13