IB-23C650M
CONTROLLER ATTRIBUTE LISTING - REGISTER DATA
Ramp/Soak Profile and Totalizer Data (registers)
Reg.
#
Description Register Value
2050R
Displayed Value
30
R _
Ramp/soak segment time remaining.
Time remaining in the currently active
ramp/soak segment.
0 to 32000 0.0 to 3200
31
R _
Current ramp/soak cycle. 0 to 65535 0 to 65535
32
R _
Current ramp/soak segment 1 to 10 1 to 10
33
R _
Floating point totalized count hi bytes.
Upper 2 bytes of totalized count in
IEEE floating point format.
Register #9, bits 1 & 0 = 0
Register #9, bits 1 & 0 = 1
Register #9, bits 1 & 0 = 2
Register #9, bits 1 & 0 = 3
IEEE Single
precision floating
point value
Same as above
Same as above
Same as above
0000000 to
9999999
000000.0 to
999999.9
00000.00 to
99999.99
0000.000 to
9999.999
34
R _
Floating point totalized count low
bytes. Lower 2 bytes of totalized
count in IEEE floating point format.
Same as Reg #33 Same as Reg #33
35
R _
Integer totalized count. Permits
transfer of totalized count in integer
format. Tops out at 65K
Register # 9, Bits 1&0 = 0
Register # 9, Bits 1&0 = 1
Register # 9, Bits 1&0 = 2
Register # 9, Bits 1&0 = 3
0 to 65535
0 to 65535
0 to 65535
0 to 65535
0 to 65535
0 to 6553.5
0 to 655.35
0 to 65.535
36
R W
Floating point totalizer preset hi bytes.
Upper 2 bytes of totalizer preset
number in IEEE floating point format.
Same as Reg #33 Same as Reg #33
37
R W
Floating point totalizer preset low
bytes. Lower 2 bytes of totalizer
preset number in IEEE floating point
format.
Same as Reg #33 Same as Reg #33
38
R W
Integer totalizer preset count. Permits
transfer of totalizer preset number in
integer format.
Same as Reg #35 Same as Reg #35
42