IB-23C650M
RS-485 COMMUNICATIONS SETUP
Table 1. RS-485 Setup Menu
Middle
Display
Bottom
Display
Entry Description
CTL MODE LAST
MANUAL
AUTO
=controller maintains the same control mode
after a communications failure has been
detected.
=controller operates in manual following a
computer failure with the output as defined in
Step 8.12.1.1.
=controller operates in automatic following a
computer failure with the set-point as defined in
Step 8.12.6.1.1.
OUTPUT LAST
NEW VALU
=control output holds at the output value prior
to the computer failure.
=control output set to value set in Step
8.12.1.1.1.
Note: This new value is used only if the
controller mode in Step 8.12.1 is manual (MAN)
and a computer failure is detected.
OUT VAL XXX Where X = any value between 0 and 100%.
This is the output of the controller if a computer
failure is detected and the controller is in
manual.
OUTPUT 2 LAST
NEW VALU
=output 2 holds at the same value prior to the
computer failure.
=output set to value set in Step 8.12.2.1.
Note: This new value is used only if the
retransmission variable in the "MA OUTP
MENU" has been selected as manual or
computer only, and if a computer failure is
detected (see Table 4 in IB-23C650 for more
information).
21