53MT6000 INSTRUCTION MANUAL
Database Editor 59
7.4.7.4 ALARM Configurable Parameters
The control module ALARM parameters can be configured by clicking on the ALARM button. The window
shown in Figure 7-13 will be displayed. The database locations where these values are stored for CON0
are shown in brackets [ ].
Figure 7-13. Alarm Parameter Configuration Window
ENTRY EXPLANATION
Tagname: Tagname of the CON module [A00].
Control Alarm Mode: This parameter is used to select the control module Alarm mode
[B335]. Available selections:
None
PA1:HI
PA2:LO
PA1:HI PA2:HI-HI
PA1:LO PA2:LO-LO
PA1:HI-DEV PA2:LO-DEV
PA1:HI PA2:LO
Alarm A: Alarm status for the selected alarm limit 1 [L110].
Alarm B: Alarm status for the selected alarm limit 2 [L111].
Control Alarm Ack: This database parameter is used to acknowledge the control
module alarms.
Alarm Limit 1: Alarm Limit value 1 [C103].
Alarm Limit 2: Alarm Limit value 2 [C104].
Alarm Dead Band: Defines a value below the high limit and above the low limit through
which the process measurement must travel before it will reset the
alarm condition. This is also known as hysteresis. [C105]
OK: Saves changes, closes window and returns to main menu.