53MT6000 INSTRUCTION MANUAL
56 Database Editor
ENTRY
EXPLANATION
Tagname: Tagname of the CON module [A00].
Output Track
Status:
Displays the current status value of the Output tracking. A
1 indicates the output value is coming from the Output
Track value. A 0 indicates the output comes from the
control modules automatic or manual output value [L105].
Output Track
Switch:
This parameter is used in conjuction with the Output Track
Enable to select output tracking [L117]:
Do Not Track
Track
Output Track
Enable:
This parameter is used to disable or enable output tracking
[L119]:
Tracking Disabled
Tracking Enabled
Hard Manual
Limit:
This parameter enables or disables the output limit
checking. When enabled, the Output High and Output Low
Limits are applied to the output signal [L122]:
Disabled
Enabled
Output: This parameter is the output of the Auto/Manual selector.
This output normally represents the final output of the
controller [C102].
Output High
Limit:
High output limit value [C109]
Output Low
Limit:
Low output limit value [C110]
Output Slew
Rate:
Output rate limit [C118]
Control Output: This displays the calculated output of the PID function
[C123].
Output Track
Value:
This parameter is the output value applied to the Auto/
Manual Selector when the Output Tracking Status is equal
to 1.
OK: Saves changes, closes window and returns to main menu.
Save: Saves changes without closing window.
Cancel: Cancels changes and returns to main menu.