MODBUS RTU
COMMUNICATIONS GUIDE
20
MOD30ML AND MODCELL MLP REFERENCE TABLES
Table 11. MOD30ML and Modcell Multiloop Processor to Host Device or PC Sample Configuration Entries
MOD30ML or Modcell Multiloop Processor Host Device or PC
Signal Source List
Data
Engineering
Range Type Entry
Modbus List
Range Scale MSC Modbus Data
Device
Range
Engineering
Range
Type Low High CL ML Number Low High Factor Connection Address Type Low High Low High Note
Floating
Point
0 100 X 1 0 100 SRWIN1 40001 WORD 0 65535 0 100
Floating
Point
-10 10 X 2 -10 10 SRWIN1 40002 WORD 0 65535 -10 10
Floating
Point
-14 0 X 3 -14 0 SRWIN1 40003 WORD 0 65535 -14 0
Floating
Point
0 80000 X 1 0 8000 SRWIN2 40101 WORD 0 65535 0 8000 10x mult
req’d
mSec
Time
0 4294967295 X 2 0 65535 1 SRWIN2 40102 WORD 0 65535 0 65535 1 mSec /
count
mSec
Time
0 4294967295 X 3 0 65535 10 SRWIN2 40103 WORD 0 65535 0 65535 10 mSec
/ count
mSec
Time
0 4294967295 X 4 0 65535 100 SRWIN2 40104 WORD 0 65535 0 65535 100
mSec /
count
mSec
Time
0 4294967295 X 5 0 65535 1000 SRWIN2 40105 WORD 0 65535 0 65535 1 Sec /
count
mSec
Time
0 4294967295 X 6 0 65535 10000 SRWIN2 40106 WORD 0 65535 0 65535 10 Sec /
count
mSec
Time
0 4294967295 X 7 0 65535 100000 SRWIN2 40107 WORD 0 65535 0 65535 100 Sec
/ count
Discrete 0 1 X 8 SRWIN2 40108 WORD 0 65535 0 1 Bit 1 of
16
Discrete 0 1 X 9 SRWIN2 40109 WORD 0 65535 0 1 Bit 1 of
16
Discrete 0 1 X 1 DRWIN1 00001 BIT 0 1 0 1 Bit 1 of 1
Discrete 0 1 X 2 DRWIN1 00002 BIT 0 1 0 1 Bit 1 of 1
Floating
Point
0 100 X 1 MRWIN1 41001 FLOAT 0 100 0 100
Floating
Point
-10 10 X 2 MRWIN1 41003 FLOAT -10 10 -10 10
Floating
Point
-14 0 X 3 MRWIN1 41005 FLOAT -14 0 -14 0
Floating
Point
0 80000 X 1 MRWIN2 41101 FLOAT 0 80000 0 80000
* NOTE: When connections are made from a source that has a variable data type,
the Range and Scale Factor fields may be enabled when they do not
apply. In this case, leave the default Range of 0 to 65535 and Scale
Factor of 1.